Power cables with extruded insulation and their accessories for rated voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV) 

IEC 60840, this International Standard specifies test methods and requirements for power cable systems for fixed installations, for rated voltages above 30 kV (Um=36kVUm​=36kV) up to and including 150 kV (Um=170kVUm​=170kV). It also separately covers cables and accessories.

1. Scope and voltage rating

IEC 60840 is specifically intended for fixed installation power cable systems, covering:

  • Voltage Range: Rated voltages above 30 kV (Um = 36 kV) up to 150 kV (Um = 170 kV) , 38/66kV,48/66kV,64/110kV,127/220kV
  • Objects: Includes single-core cables, three-core cables with individual shielding, and corresponding accessories such as terminations and joints.
  • Exclusions: The standard does not apply to special cables, such as submarine cables (which may require modified test conditions), nor does it cover transition joints between extruded and paper-insulated cables.

2. Insulation Types

The standard applies to extruded insulation power cables. The main insulation materials are:

  • XLPE (Cross-linked polyethylene) – the predominant thermosetting insulation material for this voltage range
  • HEPR (Hard ethylene propylene rubber) – an alternative thermosetting insulation material

3.Sheath / Jacket Types

The standard specifies various metallic and non-metallic sheath/jacket materials to meet different environmental requirements.

1. Metallic Sheath

Used primarily for radial waterproofing and metallic screening. As defined in Clause 4.3, common types include:

  • Lead alloy sheath
  • Aluminium tape sheath

2. Non-metallic Outer Sheath

As defined in Clause 4.4 and the new material introduced in the 2020 edition:

  • PE (Polyethylene) – e.g., HDPE, offering excellent moisture resistance and abrasion resistance
  • LSHF / ST12 (Low Smoke Halogen Free) – an environmentally friendly sheathing material first introduced in the 2020 edition. It produces low smoke and is non-toxic and non-corrosive in case of fire, making it particularly suitable for enclosed spaces with high personnel safety requirements
  • Other types – The standard also refers to specific formulations such as ST3 and ST7

4. Cable Types

1. Common Designations in China (Reference: GB/T 11017)

Chinese 64/110 kV high-voltage cables complying with IEC 60840 typically follow the national standard GB/T 11017. The designation clearly expresses the cable construction through letter codes.

Basic Format: Insulation + Conductor + Metallic Sheath + Outer Sheath

Common Designations and Explanations:

DesignationName and Construction InterpretationMain Application
YJLW02YJ (XLPE insulation) + L (Aluminium sheath) + W (Corrugated) + 02 (PVC outer sheath)Indoor, tunnel, cable trench or direct burial; can withstand certain mechanical stress
YJLW03YJ (XLPE insulation) + L (Aluminium sheath) + W (Corrugated) + 03 (PE outer sheath)Same as above, but PE outer sheath provides better moisture resistance
YJLW02-ZBase designation with -Z suffix, indicating longitudinal water blocking functionHumid environments or locations with high groundwater levels

Designation Code Explanation:

  • Conductor: Default (no prefix) or “T” added before “YJ” indicates copper conductor (e.g., TYJLW02); “L” added indicates aluminium conductor (e.g., LYJLW02).
  • Insulation: YJ represents XLPE.
  • Metallic Sheath: L represents aluminium sheath; Q represents lead sheath.
  • Outer Sheath: 02 = PVC; 03 = PE.

2. International Common Designations (European Harmonized System)

In the international market, particularly Europe, cable designations often follow HD (Harmonization Document) standards, with a naming system different from the Chinese one.

Designation ExampleName and Construction Interpretation
N2XS(FL)2YN (Conforms to HD standard) + 2X (XLPE insulation) + S (Metallic sheath/screen) + (FL) (Water blocking construction) + 2Y (PE outer sheath)
NA2XS(FL)2YBased on N2XS(FL)2Y, A indicates aluminium conductor (if starting with N without A, copper conductor is default)
(N)TMCHXOEUPrysmian flexible cable designation: TM (Extra flexible copper conductor) + CHX (HEPR insulation) + OEU (LSZH outer sheath)

3. Construction vs. Code Cross-Reference Table

Regardless of the designation system, the core purpose is to describe the cable construction. The following table helps you quickly identify what material each code represents:

ComponentCommon Chinese CodeCommon International Code
Conductor (Cu/Al)(T) / LNA (Aluminium) / default (Copper)
Insulation (XLPE/HEPR)YJ2X (XLPE) / CHX (HEPR)
Metallic Sheath (Lead/Al)Q (Lead) / L (Aluminium)S (Screen/Sheath) / (FL) Water blocking
Outer Sheath (PVC/PE/LSZH)02 (PVC) / 03 (PE)2Y (PE) / O (LSZH)

IEC 60840 Cable

FAQ

Answers To Your Most Common Questions

What types of insulation are covered by IEC 60840?

Answer:

XLPE (Cross-linked Polyethylene)

HEPR (Hard ethylene propylene rubber)

What voltage ratings of cables does IEC 60840 cover?

Answer: ICEA S-93-639 cover 38/66kV, 48/66kV, 64/110kV, 127/220kV

What is the metallic sheath material?

Answer: Lead alloy sheath and Aluminum tape sheath

Get In Touch

Let’s Build Something
Together.

No. 238, Zhenkang Road, Zhangyan Town,Jinshan District, Shanghai,China

Quick Link

Learn More About Us

About QIFAN
About QIFAN
We are a leading cable manufacturer in China with over 30 years of experience.
Customer Service
Customer Service
Exceptional Service– From First Contact to Long-Term Partnership
Quality Assurance
Quality Assurance
Advanced imported production lines; ISO 9001/14001/OHSAS 18001, TUV, VDE, UL, CE, SAA certified.