Home | Products | Cables by Standard | IEC 60840 Cable | 48/66kV Aluminum XLPE Insulated Copper-Wire Screened Power Cable

IEC 60840 Cable, Building Cable

48/66kV Aluminum XLPE Insulated Copper-Wire Screened Power Cable

High voltage power cable is applicable to being fixedly laid on the transmission and distribution line of rated voltages from 66kV up to 500kV with the use for power transmission and distribution. Laying site for instance in tunnel, pipeline and soil to transport electrical energy. Allowing for high fall or vertical installation

  • Standard :IEC 60840
  • Certificate: ISO 9001, ISO 14001, ISO 45001
  • UV Proof, Water proof

 

Application

High voltage power cable is applicable to being fixedly laid on the transmission and distribution line of rated voltages from 66kV up to 500kV with the use for power transmission and distribution. Laying site for instance in tunnel, pipeline and soil to transport electrical energy. Allowing for high fall or vertical installation

Characteristics

  • Voltage Rating: 48/66kV
  • Max. conductor temperature in service 90 °C
  • Max. Short time overload temperature(2 h)130 °C
  • Maximum conductor short time temperature 250 °C
  • Bending factor when laying
  • 20 x D single core cable
  • Metallic Screen: Copper wire

Products Construction

• Conductor: Stranded Compacted Aluminum

• Conductor Shield : Semi-conductor XLPE Compound

• Insulation: XLPE Insulation

• Insulation Shield: Semi-conductor XLPE Compound

• Metallic Screen: Copper Wire

• Outer sheath : PVC or PE

Applicable Standards

IEC 60840

Optional

Conductor can be water blocking
Anti-termite
Anti-rodent
Oil Resistance
UV Resistance

Technical Parameters

YJLV / YJLY 48/66kV Aluminum Core XLPE Insulated Copper-Wire Screened Power Cable

Nominal cross section (mm²)Conductor formDiameter (mm)Nominal insulation thickness (mm)Insulation outer diameter (mm)Copper-wire screen section (mm)Nominal sheath thickness (mm)Nominal cable outer diameter (mm)Approx. mass (kg/km) – YJLVApprox. mass (kg/km) – YJLYDC resistance at 20℃ (Ω/km)Capacitance at 20℃ (μF/km)
1×185Circular compact16.216.051.0504.066.2418037820.16400.124
1×240Circular compact18.415.051.2504.066.4428438840.12500.141
1×300Circular compact20.615.053.4504.068.6461542010.10000.151
1×400Circular compact23.415.056.2504.071.4505046190.07780.167
1×500Circular compact26.614.057.4504.072.6535749180.06050.194
1×630Circular compact30.014.060.8504.076.0597055100.04690.210
1×800Circular compact34.014.064.8504.080.0672762400.03670.222
1×800Segmented35.014.067.1504.082.3690064980.03670.231
1×1000Segmented39.014.071.1504.587.3805174540.02910.256
1×1200Segmented42.614.074.7504.590.9904183450.02470.271
1×1400Segmented45.214.077.3504.593.5978790710.02120.286
1×1600Segmented48.514.080.6504.596.81056298190.01860.299
1×1800Segmented50.814.082.9504.599.111106104250.01650.312
1×2000Segmented54.014.086.1504.5102.312132113450.01450.327
1×2200Segmented57.414.089.5504.5105.712942121280.01350.345
1×2500Segmented61.214.093.3504.5109.514054132090.01270.362

FAQ

What is considered a high voltage cable?

High voltage is defined as any voltage over 1000 volts. Those of 2 to 33 kV are usually called medium voltage cables, those over 50 kV high voltage cables.

What cable is used for high voltage?

Depending on application needs, high voltage cable typesinclude PVC (Polyvinyl Chloride) and XLPE (Cross-Linked Polyethylene) insulated cables. Among them, XLPE power cables are the most widely used due to their superior thermal and dielectric properties, making them suitable for demanding environments.

What is the difference between HV and LV cables?

Voltage Levels – HV systems operate above 1,000 volts, while LV systems stay below. Capacity – HV can handle significantly higher loads, ideal for energy-intensive operations. Infrastructure – HV requires more robust equipment, including larger switchgear and more complex cabling, than LV systems.

Are high voltage cables AC or DC?

HVDC is used for long submarine cables where AC cannot be used because of cable capacitance. In these cases special high-voltage cables are used.

How to select a high voltage cable?

Key Factors to Consider While Selecting High-voltage Cables
Understand Your Voltage Requirements: The first step in selecting the right high-voltage cable is to determine your voltage range. …
Consider the Environment: The environment where the cable will be installed plays a critical role in the cable selection process.

What gauge is HV cable?

HV cables feature a wide range of conductor sizes, measured in AWG (American Wire Guage) and, in some cases, square millimeters (mm²). The conductor size impacts the capacity and diameter of the cable. Most gauge sizes range between 2 AWG and 28 AWG. Smaller diameters are ideal for tighter tolerances.

What are high voltage cables used for?

High-voltage (HV) cable, is a highly insulated, heavy-duty cable necessary for high-voltage power transmission. It is used in instruments, ignition systems, and alternating current (AC) and direct current (DC) power transmission in many environments.

Get In Touch

Let’s Build Something
Together.

No. 238, Zhenkang Road, Zhangyan Town,Jinshan District, Shanghai,China

Quick Link

Learn More About Us

About QIFAN
About QIFAN
We are a leading cable manufacturer in China with over 30 years of experience.
Customer Service
Customer Service
Exceptional Service– From First Contact to Long-Term Partnership
Quality Assurance
Quality Assurance
Advanced imported production lines; ISO 9001/14001/OHSAS 18001, TUV, VDE, UL, CE, SAA certified.