Home | Products | Cables by Standard | IEC 60840 Cable | 37/66kV CU Core XLPE Insulated Metal-PE Composite Sheath Power Cable

IEC 60840 Cable, Building Cable

37/66kV CU Core XLPE Insulated Metal-PE Composite Sheath Power Cable

High voltage power cable is applicable to being fixedly laid on the transmission and distribution line of rated voltages from 66kV up to 500kV with the use for power transmission and distribution. Laying site for instance in tunnel, pipeline and soil to transport electrical energy. Allowing for high fall or vertical installation.

  • Standard: IEC 60840
  • Certificate: ISO9001,ISO14001, ISO45001
  • UV Proof, Flame retardant

 

Application

High voltage power cable is applicable to being fixedly laid on the transmission and distribution line of rated voltages from 66kV up to 500kV with the use for power transmission and distribution. Laying site for instance in tunnel, pipeline and soil to transport electrical energy. Allowing for high fall or vertical installation

Characteristics

  • Voltage Rating: 37/66kV
  • Max. conductor temperature in service 90 °C
  • Max. Short time overload temperature(2 h)130 °C
  • Maximum conductor short time temperature 250 °C
  • Bending factor when laying
  • 20 x D single core cable
  • Metallic Sheath: Metal-PE Composite

Products Construction

• Conductor: Stranded Compacted copper Class 2

• Conductor Shield : Semi-conductor XLPE Compound

• Insulation: XLPE Insulation

• Insulation Shield: Semi-conductor XLPE Compound

• Metallic Sheath: Metal-PE Composite

• Outer sheath : PE

Applicable Standards

IEC 60840

Optional

Conductor can be water blocking
Anti-termite
Anti-rodent
Oil Resistance
UV Resistance

Technical Parameters

YJA03 / YJA03-Z 37/66kV Copper Core XLPE Insulated Metal-PE Composite Sheath Power Cable

Nominal cross section (mm²)Conductor formDiameter (mm)Nominal insulation thickness (mm)Insulation outer diameter (mm)Copper-wire screen section (mm)Nominal sheath thickness (mm)Nominal cable outer diameter (mm)Approx. mass (kg/km)DC resistance at 20℃ (Ω/km)Capacitance at 20℃ (μF/km)
1×95Circular compact11.613.040.4504.057.334670.19300.117
1×120Circular compact13.013.041.8504.058.737800.15300.125
1×150Circular compact14.413.043.2504.060.141380.12400.133
1×185Circular compact16.213.045.0504.061.945650.09910.142
1×240Circular compact18.412.045.2504.062.149820.07540.164
1×300Circular compact20.612.047.4504.064.356690.06010.177
1×400Circular compact23.412.050.2504.067.165890.04700.197
1×500Circular compact26.612.053.4504.070.377470.03350.218
1×630Circular compact30.012.056.8504.073.791750.02830.237
1×800Circular compact34.012.060.8504.077.7109700.02210.247
1×800Segmented35.012.063.1504.080.0112200.02210.268
1×1000Segmented39.012.067.1504.585.0134220.01760.290
1×1200Segmented42.612.070.7505.089.6154420.01510.307
1×1400Segmented45.212.073.3505.092.2173970.01290.324
1×1600Segmented48.512.076.6505.095.5193100.01130.339
1×1800Segmented50.812.078.9504.596.8212730.01010.354
1×2000Segmented54.012.082.1505.0101.0234180.00900.372
1×2200Segmented57.412.085.5505.0104.4254270.00830.391
1×2500Segmented61.212.089.3505.0108.2283520.00720.411

FAQ

What is considered a high voltage cable?

A high-voltage wire (or cable) is an electrical conductor rated to carry high potential energy, typically above 1,000 volts (though often running from 35 kV to over 500 kV). These heavy-duty cables are designed to efficiently transmit massive amounts of electricity from power plants to municipal grids while minimizing energy loss.

What cable is used for high voltage?

Depending on application needs, high voltage cable typesinclude PVC (Polyvinyl Chloride) and XLPE (Cross-Linked Polyethylene) insulated cables. Among them, XLPE power cables are the most widely used due to their superior thermal and dielectric properties, making them suitable for demanding environments.

What is an hv cable?

A high-voltage cable (HV cable), sometimes called a high-tension cable (HT cable), is a cable used for electric power transmission at high voltage. A cable includes a conductor and insulation. Cables are considered to be fully insulated.

What is the difference between HV and LV cables?

Voltage Levels – HV systems operate above 1,000 volts, while LV systems stay below. Capacity – HV can handle significantly higher loads, ideal for energy-intensive operations. Infrastructure – HV requires more robust equipment, including larger switchgear and more complex cabling, than LV systems.

What type of wire is used for high voltage?

The most common materials used in HV cables are copper and aluminum. Most applications favor a copper conductor because stranded copper wire is very flexible and an excellent conductor. Aluminum is lighter weight and less costly, but it has a slightly lower conductivity.ons.

Do HV cables have a neutral?

Neutral lines are commonly used in low-voltage distribution systems, but not in high-voltage transmission. Here’s why: In electrical systems, the term neutral typically refers to a point in the circuit that is at zero potential relative to the ground. The neutral wire serves as a return path for current.e.

Get In Touch

Let’s Build Something
Together.

No. 238, Zhenkang Road, Zhangyan Town,Jinshan District, Shanghai,China

Quick Link

Learn More About Us

About QIFAN
About QIFAN
We are a leading cable manufacturer in China with over 30 years of experience.
Customer Service
Customer Service
Exceptional Service– From First Contact to Long-Term Partnership
Quality Assurance
Quality Assurance
Advanced imported production lines; ISO 9001/14001/OHSAS 18001, TUV, VDE, UL, CE, SAA certified.